Flow uniformity: max/min branch flow difference ≤ arithmetic mean 10%
Test Systems
GtestWorks Automated Testing Platform
VectWorks 3.0 Electrical Performance Test Software
GB/T 48023-2026 is China's first national-level unified standard for cold plate liquid cooling systems, covering the full lifecycle of data center cold plate liquid cooling systems from design, manufacturing, deployment to operations. The standard was issued on July 30, 2026 and officially implemented on February 1, 2027.
This page systematically outlines the framework and core content of the GB/T 48023-2026 standard for quick reference.
Flow uniformity: max/min branch flow difference ≤ arithmetic mean 10%
Heat transfer capacity: actual ≥ 95% of design load at rated conditions
Standard official effective date
Cold plate share of liquid cooling market
| Item | Content |
|---|---|
| Standard No. | GB/T 48023-2026 |
| Chinese Name | 数据中心冷板式液冷系统技术规范 |
| English Name | Technical specifications for cold plate liquid cooling system of data center |
| Standard Type | Recommended National Standard (GB/T) |
| Issue Date | July 30, 2026 |
| Effective Date | February 1, 2027 |
| Pages | 24 pages |
| Word Count | 35 thousand characters |
| Issued by | State Administration for Market Regulation, Standardization Administration of China |
| Administered by | National Information Technology Standardization Technical Committee (SAC/TC 28) |
| Lead Drafter | Dawning Data Infrastructure Innovation Technology (Beijing) Co., Ltd. |
GB/T 48023-2026 is China's first national-level unified standard for cold plate liquid cooling systems, covering the full lifecycle of data center cold plate liquid cooling systems from design, manufacturing, deployment to operations. The issuance of this standard marks the formal transition of cold plate liquid cooling technology from "sporadic pilots" to "large-scale deployment," ending the industry's long-standing lack of unified guidelines and product incompatibility.
| Chapter | Title |
|---|---|
| 1 | Scope |
| 2 | Normative References |
| 3 | Terms and Definitions |
| 4 | Abbreviations |
| 5 | System Composition |
| 6 | Technical Requirements |
| 7 | Test Methods |
| Appendix A (Normative) | Secondary side coolant indicator requirements and test methods |
| Appendix B (Normative) | Secondary side system installation, pressure holding, and flushing |
| Pain Point | Specific Manifestation | Impact |
|---|---|---|
| Lack of Unified Technical Standards | Cold plate dimensions, quick connect fitting specs, and CDU interface standards vary by manufacturer | Manufacturer A's cold plate cannot adapt to Manufacturer B's manifold; poor system compatibility |
| High Customization Costs | Nearly every project requires a new round of customization adaptation | Design costs and delivery cycles remain high |
| Unclear Responsibility Boundaries | Data center construction parties, cooling suppliers, and整机 manufacturers have unclear responsibility divisions | Mutual blame when faults occur |
| Lack of Standards for Safe Operations | Leakage monitoring, corrosion prevention, and coolant selection have no unified requirements | Market has widespread concerns about liquid cooling safety |
| No Threshold for Long-term Reliability | Lack of unified testing and verification system | Product quality is uneven |
Single chip power consumption from 200W→700W→1000W+; air cooling hits physical ceiling; single cabinet power density from 80kW→200kW→1MW+
New data center PUE requirements ≤1.25 in most regions, core areas ≤1.15; air cooling PUE typically 1.8, cooling electricity consumption accounts for 40%+ of total power
158 intelligent computing bids above 100 million RMB in first 7 months of 2026; winning amounts exceed 113 billion RMB; customization costs become a "tax" on the industry chain
GB/T 48023-2026 is a Recommended National Standard (GB/T), not a mandatory standard (GB). However, in practical applications, large intelligent computing centers and operator procurement typically write national standards into technical bid requirements, making them contract-level hard thresholds once referenced.
| Dimension | Content |
|---|---|
| Applicable Scenarios | Design, manufacturing, deployment, and operations of data center cold plate liquid cooling systems |
| Not Applicable | Phase-change cold plate liquid cooling systems (two-phase cold plate is not within scope) |
| Applicable Objects | Liquid cooling product and service providers, application units, and computing facility users |
| Timeline | Event |
|---|---|
| July 30, 2026 | Standard officially issued (Standardization Administration Announcement No. 33, 2026) |
| August 2026 ~ January 2027 | Transition preparation period (~6 months) |
| February 1, 2027 | Standard officially implemented |
| Term | English | Definition |
|---|---|---|
| Cold Plate | cold plate | A cavity with internal fluid channels that utilizes coolant circulation within these channels to achieve heat dissipation |
| Coolant | coolant | The medium that absorbs and transmits heat in a liquid cooling system |
| Cold Plate Liquid Cooling System | cold plate liquid cooling system | A system that transfers heat from IT equipment components to enclosed circulating coolant through cold plates, exchanges heat through one or more cooling circuits, and ultimately dissipates heat to the outdoors |
| Secondary Side Cooling System | secondary side cooling system | A cooling system that absorbs heat from IT equipment components through enclosed coolant circulation and exchanges heat with the primary side cooling system |
| Primary Side Cooling System | primary side cooling system | A cooling system that dissipates heat from the secondary side cooling system to the outdoor atmospheric environment or through a heat recovery system |
The standard clearly defines two core parts of the cold plate liquid cooling system:
CDU is the hub for heat exchange between primary and secondary sides, providing secondary side flow distribution, pressure control, physical isolation, and anti-condensation functions.
| Abbreviation | Full Name | Chinese Meaning |
|---|---|---|
| CDU | Coolant Distribution Unit | 冷量分配单元 |
| IT | Information Technology | 信息技术 |
| PUE | Power Usage Effectiveness | 电能利用效率 |
| TIM | Thermal Interface Material | 导热界面材料 |
| Indicator Category | Specific Indicator | Quantitative Requirement |
|---|---|---|
| Flow Uniformity | Secondary side piping branch flow deviation | Difference between max and min ≤ 10% of arithmetic mean of all branch flows |
| Heat Transfer Capacity | Actual system heat transfer at rated conditions | Shall be no less than 95% of design load |
| Pressure Loss | System piping resistance | Shall comply with design requirements |
| Temperature Uniformity | Secondary side supply/return water temperature | Shall comply with design requirements |
| Specification Module | Core Requirements | Pain Point Solved |
|---|---|---|
| Cold Plate Assembly | Unified indicators for materials, dimensions, thermal performance, and reliability | Each manufacturer's cold plates are incompatible |
| Quick Connect Devices | Interface dimensions, sealing performance, and insertion/removal life standardization | Fittings not universal, leakage risk |
| CDU | Heat exchange performance, control precision, and safety protection requirements | Lack of unified basis for cabinet-to-cabinet heat exchange |
| Hydraulic Calculation Model | Unified calculation methods for piping resistance and flow distribution | Each manufacturer's design parameters are not comparable |
| Testing and Verification Methods | Standard procedures for performance testing and reliability testing | No basis for acceptance |
| Deployment and Operations | Installation specifications, operation monitoring, and maintenance cycle requirements | Lack of operations standards |
| Testing Level | Test Item | Corresponding Standard Chapter |
|---|---|---|
| Component-level | Cold plate thermal performance testing | Chapter 7 |
| Component-level | Quick connect sealing testing | Chapter 7 |
| Component-level | CDU performance testing | Chapter 7 |
| System-level | Flow uniformity testing | Chapter 7 |
| System-level | Heat transfer capacity testing | Chapter 7 |
| System-level | Pressure loss testing | Chapter 7 |
| Safety-level | Leakage detection testing | Chapter 7 |
| Inspection Item | Acceptance Standard |
|---|---|
| Flow testing | Within design flow ±5% |
| Temperature control accuracy | Secondary side supply water temperature stable at set value ±0.5°C |
| Leakage detection | Simulate leakage; trigger alarm and auto-shutdown within 2s |
| Redundant switching | Backup pump input within 5s |
| Noise | ≤75 dB(A) at 1m from CDU |
| Communication | Normal communication with BMS; data refresh cycle ≤5s |
| Coolant Type | Main Components | Advantages | Applicable Scenarios |
|---|---|---|---|
| PG 25 | 25% propylene glycol + 75% deionized water | Easy maintenance, extremely low toxicity, anti-freeze | Large data centers, long-link systems (mainstream trend) |
| EG 25 | 25% ethylene glycol + 75% deionized water | Lower cost, anti-freeze | Cost-sensitive projects |
| Deionized Water | Pure water | Optimal thermal conductivity, low cost | Short-link, small-scale systems, indoor constant temperature environments |
| Process | Core Requirements |
|---|---|
| Installation | Piping laying, fitting connections, and bracket fixation shall comply with design documents and construction specifications |
| Pressure Holding | Pressure holding test shall be conducted after system installation to verify sealing and detect leakage in piping and fittings |
| Flushing | Piping flushing shall be conducted before system operation to remove construction residues and ensure coolant circulation system cleanliness |
| Acceptance | Data center infrastructure overall construction and acceptance shall comply with standard requirements |
| Standard No. | Standard Name | Reference Role |
|---|---|---|
| GB/T 8446.2 | Heat sinks for power semiconductor devices Part 2: Thermal resistance and flow resistance measurement methods | Cold plate thermal performance test method reference |
| GB 50242 | Code for acceptance of construction quality of building water supply and drainage and heating engineering | Piping installation and pressure holding test acceptance |
| GB 50243 | Code for acceptance of construction quality of ventilation and air conditioning engineering | Cooling system construction acceptance |
| GB 50462 | Standard for construction and acceptance of data center infrastructure | Data center overall construction and acceptance framework |
| GB 50738 | Code for construction of ventilation and air conditioning engineering | Cooling system construction process specification |
| Standard No./Plan No. | Name | Status |
|---|---|---|
| T/CECS 1722-2024 | Liquid cooling data center technical requirements | Issued |
| T/TAF 324-2026 | Cold plate liquid cooling cabinet system technical requirements and test methods | Issued |
| 20263064-Z-469 | General design guide for immersion liquid cooling power modules for data centers | Being drafted |
| Indicator | 2025 | 2026 (E) | 2027 (E) |
|---|---|---|---|
| Global AI chip liquid cooling penetration | 33% | 53% | ~60% |
| China liquid cooling server penetration | 20% | 37% | >50% |
| Cold plate share of liquid cooling market | 85%+ | 80%-85% | 75%-80% |
| China liquid cooling data center market size | — | 232.5 billion RMB | — |
| Segment | Value Share | Core Companies |
|---|---|---|
| Cold Plate Assembly | 35%-40% | Envicool (domestic market share >30%), AVIC Jicheng, Feirongda |
| CDU | 25%-30% | Shenling Environment (domestic market share #1), Vertiv, Envicool |
| Quick Connect Fittings | 5%-10% | AVIC Jicheng (UQD included in NVIDIA MGX ecosystem) |
| Coolant | ~10% | Various specialized formulation manufacturers |
| Piping System | 5%-10% | Wanda Technology, Yizhou Data |
Clarification: The "T" in GB/T stands for "Recommended" and is not itself a mandatory standard. However, in practical projects, large intelligent computing centers and operator procurement typically write national standards into technical bid requirements, making them contract-level hard thresholds once referenced.
Clarification: The national standard focuses on cold plate liquid cooling systems and explicitly does not apply to phase-change cold plate liquid cooling systems (two-phase cold plate). Immersion liquid cooling standardization work is being advanced separately.
Clarification: The standard applies to new design, manufacturing, and deployment; it does not apply retroactively to completed projects. Liquid cooling initial investment is 30%-50% higher than air cooling, but 5-year TCO is 18%-25% lower than air cooling.
Clarification: The standard is administered by the National Information Technology Standardization Committee, organized by the China Electronics Standardization Institute, with participating units covering multiple segments of the industry chain (led by Dawning Data Infrastructure, jointly with Huawei, Alibaba Cloud, Vertiv, Schneider Electric, and dozens of other industry-university-research-user units).
Clarification: Cold plate liquid cooling system is a complete engineering system including quick connect fittings, manifolds, piping systems, CDU, coolant, monitoring systems, safety protection, and other full-chain components.
Two-phase cold plates use coolant phase change for more efficient heat transfer (heat dissipation capacity up to 385W/cm²), but standardization is low, limiting short-term adoption.
PG 25, EG 25, and deionized water have not yet achieved complete unification. Each manufacturer's functional additive formulations are core technical secrets and not disclosed externally.
The actual enforcement effectiveness depends on downstream bid inviters' references, third-party testing institutions' capability building, and industry chain parties' self-discipline levels.
A: Applicable to the full lifecycle of design, manufacturing, deployment, and operations of data center cold plate liquid cooling systems. Not applicable to phase-change cold plate liquid cooling systems (two-phase cold plate).
A: The standard was issued on July 30, 2026 and officially implemented on February 1, 2027, with a transition period of approximately 6 months. Teams planning or bidding intelligent computing projects before the standard implementation date should prepare technical specifications according to national standard requirements.
A: A Recommended National Standard (GB/T). "T" stands for "Recommended." Non-compliance does not result in administrative penalties, but large intelligent computing projects and operator procurement typically write national standards into technical bid requirements, making them contract-level hard thresholds once referenced.
A: Flow uniformity: the difference between maximum and minimum branch flow rates in the secondary side piping shall not exceed 10% of the arithmetic mean of all branch flow rates. Heat transfer capacity: under rated conditions, the actual system heat transfer capacity shall be no less than 95% of the design load.
A: Cold plate liquid cooling accounts for over 85% of the current liquid cooling market, with the highest technology maturity, lowest retrofit difficulty, and most complete industry ecosystem. NVIDIA GB200/GB300/Vera Rubin platforms all adopt cold plate solutions.
A: CDU is the hub for heat exchange between primary and secondary sides, providing secondary side flow distribution, pressure control, physical isolation, and anti-condensation functions. The standard formally incorporates CDU functional positioning into the specifications.
A: Both Appendix A and Appendix B are Normative Appendices with equal binding force as the main technical requirement text and are mandatory provisions.
A: Appendix A specifies coolant physicochemical performance indicators (freezing point, boiling point, pH value, conductivity, etc.) and performance indicators (corrosion inhibition, thermal stability, etc.) along with corresponding test methods. Currently, the industry is trending toward PG 25 (25% propylene glycol + 75% deionized water).
| No. | Source | Link |
|---|---|---|
| 1 | China Standards Online Service | https://www.spc.org.cn/... |
| 2 | China Electronics Standardization Institute | https://www.cesi.cn/... |
| 3 | Standard Full Text (book118) | Standard Original PDF |
| 4 | Yang Xin Ming Xue (TouTiao) | Standard Core Content Interpretation |
| 5 | Cold Plate Liquid Cooling National Standard is Here (TouTiao) | Six Major Specification Modules Analysis |
Disclaimer: This article interprets GB/T 48023-2026 based on public sources for reference only. The specific technical requirements of the standard shall prevail based on the official published version of the national standard.